Design density & area of operation
| Standard | NFPA 13 |
| Hazard class | Ordinary Hazard Group 1 |
| Density | 0.15 gpm/ft² over 1500 ft² |
| Area of operation | 139 m² |
Typical occupancies
- Car parks
- Bakeries
- Canneries
What this means for a real project
NFPA 13 Ordinary Hazard Group 1 fixes the pair of numbers — design density and area of operation — that drive the most-remote hydraulic calculation. The pump duty point, riser diameter and pipe schedule all flow from this classification. Pick the wrong class and the entire system is mis-sized.