EN 12845 · Europe

EN 12845 Ordinary Hazard Group 2 (OH2)

Commercial laundries, bakeries, parking garages and similar light-industrial.

Design density & area of operation

StandardEN 12845
Hazard classOrdinary Hazard Group 2 (OH2)
Density5.0 mm/min
Area of operation144 m²

Typical occupancies

  • Car parks
  • Bakeries
  • Commercial laundries

What this means for a real project

EN 12845 Ordinary Hazard Group 2 (OH2) fixes the pair of numbers — design density and area of operation — that drive the most-remote hydraulic calculation. The pump duty point, riser diameter and pipe schedule all flow from this classification. Pick the wrong class and the entire system is mis-sized.

In FireTwin AI you set the hazard class once per zone; layout, hydraulics and BOM recalculate inline and flag any rule that fails before the design leaves the screen.