EN 12845 · OH2

Car park fire sprinkler design

Enclosed car parks (including EV-charging decks) are designed OH2 under EN 12845. Battery fire risk increasingly drives additional measures such as deluge zones in EV bays.

Design parameters

StandardEN 12845
Hazard classOH2
Design density5.0 mm/min
Area of operation144 m²

Design notes

  • Use upright heads with deflectors clear of soffit services
  • Add deluge or watermist in EV charging zones where required
  • Frost protection: dry pipe or antifreeze loop for ramps
  • CO/NO₂ ventilation interlock for smoke clearance

Typical equipment

  • Upright K115 sprinklers
  • Dry pipe valve set
  • Diesel pump + tank
  • Hydrant ring 4 bar