EN 12845 · OH1

Office building fire sprinkler design

Open-plan and cellular offices fall under OH1. Drop ceilings, large floor plates and frequent fit-out churn drive the design — modular branch lines and quick-isolation valves matter as much as the head count.

Design parameters

StandardEN 12845
Hazard classOH1
Design density5.0 mm/min
Area of operation72 m²

Design notes

  • Plan zone valves per tenant floor for fit-out flexibility
  • Use concealed heads in client-facing areas
  • Coordinate with BMS for flow-switch monitoring
  • Allow for future densification in core areas

Typical equipment

  • Concealed pendent K80
  • Zone control valves per floor
  • Jockey pump + main pump
  • Inspector test connection per floor