Design parameters
| Standard | NFPA 13 |
| Hazard class | Extra Hazard Group 2 |
| Design density | 0.40 gpm/ft² over 2500 ft² |
| Area of operation | 232 m² |
Design notes
- ESFR design pressure typically 50 psi (3.5 bar) at the head
- Clear flue spaces between racks per NFPA 13 §17.2
- 12 most-remote heads operating in design calculation
- Yard hydrants 1500 gpm minimum
Typical equipment
- ESFR K360 sprinklers
- DN200 wet alarm valve
- Diesel + electric pump set 1500 gpm
- Yard hydrants 100 m spacing