NFPA 13 · Ordinary Hazard Group 1

Data center fire sprinkler design

White-space, MEP rooms and BMS galleries in data centres are typically pre-action sprinkler systems combined with VESDA early detection and inert-gas suppression in critical halls.

Design parameters

StandardNFPA 13
Hazard classOrdinary Hazard Group 1
Design density0.15 gpm/ft² over 1500 ft²
Area of operation139 m²

Design notes

  • Pre-action double-interlock to prevent accidental discharge
  • VESDA aspirating detection in every white-space row
  • Inert gas (IG-541 / Novec 1230) for two-hour critical loads
  • Sprinkler-free zones above busbar where standards permit

Typical equipment

  • Pre-action valve set
  • VESDA HSSD
  • IG-541 cylinders + selector valves
  • Dry-pipe risers in white space